background image

Diesel Generator Set

 

X1.3 Series

20 kVA, 16 kWe Prime

Latest Technology And Unmatched
Performance

ƒ

ƒ

The Cummins

®

 X1.3 seriesrugged engine and world 

class Stamford alternator powered diesel generator 
set

ƒ

ƒ

Advanced in-cylinder technology to meet latest 
emission norms without any after-treatment device.

ƒ

ƒ

Best in class transient response

ƒ

ƒ

High altitude capabilities

ƒ

ƒ

Smart aesthetic and superior finish

ƒ

ƒ

Compact in size with optimum power to weight ratio

Environment Friendly Power

ƒ

ƒ

Class defining technology engine is designed to meet 
stringent exhaust emission tests as per revised MoEF 
norms, thus offering environment friendly power.

ƒ

ƒ

The Cummins

®

 diesel generator sets are available with 

the lowest noise levels in its range

Lowest Operating Cost and 

Comprehensive Warranty

ƒ

ƒ

Highly reliable and durable product

ƒ

ƒ

All elements are designed to work together to 
maximize efficiency even at part loads, offering the 
advantage of lowest operating costs

ƒ

ƒ

500 Hours/ 1 year service interval

ƒ

ƒ

Industry acknowledged best-in-class comprehensive 
warranty on the entire package including rubber 
components 

Single Source Power Assurance

ƒ

ƒ

All the major components – the engine, alternator, 
control system and canopy are designed, 
manufactured and tested by Cummins India 

ƒ

ƒ

Best and Largest customer support network in India, 
capable of providing round-the-clock service and 
spares support

ƒ

ƒ

All these things put together, Cummins

®

 offers you 

SINGLE SOURCE POWER ASSURANCE

Specification Sheet

background image

Engine

ƒ

ƒ

Cummins

®

 X1.3 series, 2 cylinder, In-line 4 stroke, radiator 

cooled engine

ƒ

ƒ

Well designed air handling system with

 

— Dry type, replaceable paper element air cleaner with 

restriction indicator 

 

— Air to air aftercooling

 

— Optimised turbocharger for increased altitude 

capabilities

ƒ

ƒ

Best in class fuel economy with 

 

— Inline fuel pump with A1 class mechanical governing

 

— Spin on fuel filter

ƒ

ƒ

Standard integral set-mounted radiator system, designed 
and tested for 50°C ambient temperatures

ƒ

ƒ

Full flow spin on lube oil filter

ƒ

ƒ

First fill of lube oil and coolant

ƒ

ƒ

First fill of lube oil and coolant

ƒ

ƒ

Electrical starter motor with soft start engagement feature 

ƒ

ƒ

Battery charging alternator

ƒ

ƒ

1 x 12 V DC batteries

Alternator

ƒ

ƒ

Stamford S0L2 alternator frames from Cummins Generator 
Technologies

ƒ

ƒ

Brushless type, Screen protected, Revolving field, Self 
excited alternator conforming to IS/IEC 60034-1

ƒ

ƒ

Better motor starting capability

ƒ

ƒ

Best in class efficiency

ƒ

ƒ

Compact design with sealed bearings for longer life and 
lesser maintenance

ƒ

ƒ

Impregnation on all wound components for better 
mechanical strength

Silencer

ƒ

ƒ

Critical grade silencer suitably optimised to meet 
stringent sound emission standards laid down by MoEF / 
CPCB

Mounting Arrangement

ƒ

ƒ

Engine and alternator are mounted on a common MS 
fabricated base frame with AVM pads.

ƒ

ƒ

Base frame with integral fuel tank is provided with drain 
plug, air vent, inlet and outlet connection, level indicator and 
provision for cleaning

Optional

ƒ

ƒ

Engine: 

Coolant heater, Oil drain pump, 

ƒ

ƒ

Alternator: 

Auxiliary windings

ƒ

ƒ

Control Panel:

 Microprocessor / relay based AMF control 

panel

ƒ

ƒ

Others: 

Trolley mounted mobile sets

Diesel Generator Set X1.3 Series

Specification Sheet

PS0600 Features

Cummins

®

 PowerStart

TM

 

PS0600 control is a 
microprocessor based 
generator set monitoring 
and control system. AMF 
Functionality is inbuilt and this 
control includes an intuitive 
operator interface that allows 
for complete generator set control as well as system metering, 
fault annunciation, confi guration, and diagnostics.

ƒƒ

AMF Functionality

ƒƒ

Intuitive operator interface which includes LED backlit 
128X64 pixel graphic display with tactile feel soft-switches. 
Indications - Generator set, Utility Status Lamp.

ƒƒ

Remote Start-Stop

ƒƒ

Engine Metering: Oil pressure, Engine temperature, Starting 
battery voltage, Engine running hours

ƒƒ

AC Alternator Metering: L-L Voltage and L-N Voltage, 
Current (phase and total), kVA (phase and total) and 
Frequency, kwh, Total & per phase (kw & kVA), PF, Utility 
Voltage and Freq.

ƒƒ

�Engine Protection: Low lube oil pressure, High/Low coolant 
temperature, Battery Over/Under/Weak Volts, Fail to Crank/
Start, Sensor failure, Cranking lockout, Low fuel level.

ƒƒ

AC Alternator Protection: Over/Under Voltage, Over/Under 
Frequency, Loss of AC Sensing, Overspeed, Over Current.

ƒƒ

Data Logging: Engine Hours, Control Hours and upto 5 
recent fault codes

ƒƒ

Confi gurable glow plug control

ƒƒ

12/24 Volt DC operation

ƒƒ

Sleep mode

ƒƒ

Modbus interface (RS485 RTU)

ƒƒ

InPower compatible (PC based service tool)

ƒƒ

Certifi cations - meets the requirement of relevant ISO, EN, 
Mil Std. and CE standards

ƒƒ

Maintenance due alarm based on Engine Run Time and due 
date

ƒƒ

Exercisor scheduler

Control Panel

Control panel is manufactured with 14/16 gauge CRCA sheet 
and is powder coated for weather-proof and long lasting fi nish.
The control panel consists of the following parts:

ƒƒ

PS0600 controller

ƒƒ

Aluminum bus bars with suitable capacity with incoming/
outgoing terminals

ƒƒ

Indicating lamps for ‘Load ON’ and ‘Set Running’

ƒƒ

Instrument fuses duly wired and ferruled

ƒƒ

Circuit breakers of suitable rating with overload and short 
circuit protections

background image

Acoustic Enclosure

ƒ

ƒ

Specially designed to meet stringent MoEF/ CPCB norms of 
75 dBA @ 1mtr at 75% load under free field conditions

ƒ

ƒ

The acoustic enclosure is made of CRCA sheets in munsel 
green shade and a structural/ sheet metal base frame 
painted in black

ƒ

ƒ

High quality noise absorbant and fire-retardant grade 
acoustic insulation material (P.U. Foam) complying to 
IS 8183

ƒ

ƒ

Two point lifting for easy handling at customer site

Technical Data

Generator Set Specification

Model 

C20D5P

C18.5D5P

Duty

Prime

Prime

Power Rating kVA / kWe 

20/16

18.5/14.8

No. of Phases

3 Phase

1 Phase

Output Voltage (V)

415 

230

Power Factor 

0.8 (lagging)

0.8 (lagging)

Current (3 phase/ 1 phase) (A)

28

80

Frequency (Hz) and RPM

50 Hz, 1500 RPM

50 Hz, 1500 RPM

Engine Specifications

Make 

Cummins

Cummins

Model 

X1.3TAA-G7

X1.3TAA-G7

MoEF Certified Power (bhp)

25.2

25.2

Required Power for Rated kVA (bhp)

25.2

24.7

Cooling 

Liquid Cooled
(EG Compleat 50:50)

Liquid Cooled
(EG Compleat 50:50)

Aspiration

Turbocharged,
Charge Air Cooled

Turbocharged,
Charge Air Cooled

No. of cylinders 

2, In-line

2, In-line

Bore (mm) x Stroke (mm) 

95 x 91

95 x 91

Compression ratio

18.3:1

18.3:1

Displacement (litre) 

1.29

1.29

Fuel 

High Speed Diesel

High Speed Diesel

Fuel consumption @75% load
with radiator and fan* (litre/hr)

3.86

4.1

Fuel consumption @100% load
with radiator and fan* (litre/hr)

5.09

5.25

Performance class of generator set

ISO 8528-5 G2

ISO 8528-5 G2

Starting system 

12 V DC Electrical

12 V DC Electrical

Lube oil specification 

CH4 15W40

CH4 15W40

Lube oil sump capacity, High-Low level (litre) 

4-3

4-3

Total lubrication system capacity (litre) 

4.5

4.5

Total coolant capacity (litre) 

7.3

7.3

Exhaust pipe size (inch)

2

2

Total wet weight (Engine+Radiator)

##

 (kg)

190

190

Length x Width x Height (Engine) (mm)

481 x 715 x 662

481 x 715 x 662

Mean piston speed (m/s)

4.6

4.6

Combustion air intake @100% load (±5%) (cfm)

59.1

59.1

Exhaust Temperature (°C)

305

305

Alternator Specification

Make 

Stamford (CGT)

Stamford (CGT)

Alternator frame

S0L2-M1

S0L2-U1

Enclosure

IP 23

IP 23

Voltage regulation (Max.) 

±1%

±1%

Class of Insulation 

H Class

H Class

Winding Pitch

2/3 

2/3 

Stator Winding

Double layer lap

Double layer lap

Rotor

Dynamically Balanced

Dynamically Balanced

Waveform distortion/ Total Harmonic Distortion 

No load < 1.5 %, Non
distorting balanced
linear load < 5 %

No load < 1.5 %, Non
distorting balanced
linear load < 5 %

Maximum Unbalanced Load across phases

#

less than or equal to 25%

less than or equal to 25%

Telephonic Harmonic factor

< 2%

< 2%

ƒ

ƒ

Designed to have optimum serviceability

ƒ

ƒ

Air inlet louvers specially designed to operate at rated load

ƒ

ƒ

Made on special purpose CNC machines for consistency in 
quality and workmanship

ƒ

ƒ

11 tank pretreatment process and UV resistant powder 
coating of all parts to withstand extreme environment

ƒ

ƒ

Use of special hardware for longer life

ƒ

ƒ

Flush styling - no projections

ƒ

ƒ

Fluid drains for lube oil and fuel

ƒ

ƒ

Fuel filling arrangement inside the enclosure

* Fuel consumption data is based on diesel having specific gravity of 0.85 and conforming to IS:1460. Fuel consumption tolerance is +5% 

#

 With the condition that none of the phases exceeds its rated current

Diesel Generator Set X1.3 Series

Specification Sheet

background image

Cummins India Limited 

Power Systems Business

Cummins India Office Campus

Tower-A, 8

th

 Floor, S. No. 21,  

Balewadi, Pune – 411 045 (India)

Email: cpgindia@cummins.com

www.cumminsindia.com

“Our energy working for you.”

Cummins is registered trademarks of Cummins Inc.

 

Specifi cations are subject to change without notice.

 

PSBU/016/X1.3/HD/MP/R

evision-2 (04-2018)

Visit our facebook page at : 
Cummins Power Generation India

Typical Enclosed Genset Dimensions

Genset 
Model

Rating 
(kVA)

Length 
(mm)

Width 
(mm)

Height 
(mm)

Wet Weight

##

 

(kg)

Standard Fuel tank 
Capacity (litre)

C20D5P

20/18.5

1780

940

1100

720

63

##

 Approximate Weight

Rating Definitions

Prime Power (PRP):

Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528.  

Conformance Standards

ƒ

 

IS/IEC 60034-1 

ƒ

 

ISO 8528 

ƒ

 

ISO 9001 

ƒ

 

ISO 1460

Authorised Representative

Cummins Power Systems Offices

Bengaluru:  

Tel.: (080) 2325 9161 / 63, 2325 9165 / 67
Fax: (080) 2325 9164

Chandigarh:  

Tel.: (0172) 224 0371-73
Fax: (0172) 224 0372

Chennai:  

Tel.: (044) 2446 8110 / 2446 8113
Fax: (044) 2491 1120

Gurgaon:  

Tel.: (0124) 391 0900-01
Fax : (0124) 391 0916

Hyderabad:  

Tel.: (040) 2340 9970 / 2340 9980
Fax. (040) 2340 9990

Jaipur:  

Tel.: (0141) 236 4944
Fax: (0141) 403 8794

Kolkata:  

Tel.: (033) 2287 8065 / 2287 2481
Fax: (033) 2290 3839

Lucknow:  

Tel.: (0522) 230 5049 / 230 5059
Fax: (0522) 230 5035

Mohali:  

Tel.: (0172) 224 0371 / 72 / 73
Fax: (0172) 224 0371 / 72 / 73

Vadodara:  

Tel.: (0265) 233 0627 / 3053627
Fax: (0265) 234 0623

Diesel Generator Set X1.3 Series

Specification Sheet