Specification sheet
Reliable and durable
Cummins
®
‘K50 series’ diesel engine with strong
regrindable crankshaft, high strength connecting
rod, low pressure fuel lines, STC (Step Timing
Controls) injectors and high volume coolant system
make ‘K50 series’ generating sets, more reliable
and durable. Engines have clocked millions of hours
operating in some of the world’s most demanding
conditions. Current engines are regularly upgraded
with new technologies for better performance and
economy. The ultimate proof of superior
performance and reliability is the fact that Cummins
®
entities worldwide source these engines from
Cummins India for their markets.
Unmatched warranty
- Cummins® ‘K50 series’ diesel engine
generating sets are a truly cost effective solution
to long term power need backed by industry best,
2 years / 5000 hrs warranty, for the entire
generating set.
Cummins advantage
Special features of Cummins
®
‘K50 series’ engines
like STC (Step Timing Controls) injectors, low
temperature aftercooler, square cumbustion
chamber, optimised turbocharging and precision
heavy duty camshaft make these engines the
ultimate in exceptional fuel efficiency all across the
operating range.
Standard scope
Engine:
Cummins
®
‘K50 series’ direct injection, water
cooled
engine, 16 cylinder, 4 stroke, rated at 1500 RPM,
conforming to
ISO 3046 /
I
S
13018
has the following specifications:
-
Cummins PT fuel pump
-
Cummins heavy duty
E
STC injectors
-
Holset turbocharger, pulse tuned exhaust manifold,
stainless steel exhaust flexible connections
-
Radiator or heat exchanger, coolant inhibitor
-
Plate type lube oil cooler
-
Outboard aftercoolers
-
Full flow paper element filters - fuel, lube oil and by-pass
-
Dry type replaceable paper element air cleaner with
restriction indicator
-
Flywheel housing & flywheel to suit single/ double bearing
alternator
-
Holset flexible coupling for double bearing alternator
-
Starting motor – Electric, battery charging alternator
-
Cummins PowerCommand
®
microprocessor based
genset
controller
-
First fill lube
oil and coolant
Alternator:
Stamford brushless alternator
-
Seperately excited, self-regulated -
Class ‘H’ insulation
-
Salient pole revolving field
-
Single bearing
-
PMG standard
-
Space heater & RTD & BTD's only sensor - (without scanner)
Accessories:
- Silencer suitably optimized to reduce noise
- Sturdy base rail
- 990 ltrs. free standing fuel tank
- 4 x 12 V dry, uncharged batteries with connecting leads
and terminals
Diesel Generator Set
K50 Series
1000-1200 kWe, 1250-1500 kVA Prime
- With superior experience in
technology, design capability
and commitment reliability and
quality we offer an unmatched
5 years or 5
0
00 hours
(including above 2 years)
warranty coverage on 5
critical components (5C) of the
engine – Cylinder Head, Camshaft, Crankshaft,
Cylinder Block, Connecting Rod against
manufacturing defect
Single source power assurance
Design, manufacture and testing of engine, alternator and other
accessories is done by
Cummins Group of companies for
optimum
performance and is backed by a countrywide
product support network with a single source responsibility
for the entire package.
Optionals
Engine:
Heavy duty air cleaner, Lube oil / Coolant heater
with thermostatic switch
Alternator:
Double bearing
Control Panel:
AMF control panel, Battery charger,
Remote/Auto start panel, Auto/Manual synchronizing panel,
Audio/Visual annunciation for faults
Control panel: PowerCommand
®
PC 3.3
The PowerCommand
®
control system is
an integrated microprocessor based
generator set control system providing
voltage regulation, engine protection,
alternator protection, operator interface
and isochronous governing.
AmpSentry
– Includes integral AmpSentry protection, which
provides a full range of alternator protection function which are
matched to the alternator provided.
Power management
– Control function provides battery
monitoring, testing and a smart starting control system.
Advanced control methodology
– Three phase sensing, FET
based full wave rectified voltage regulation and a PWM output for
stable operation with all load types.
Communications interface
– Control comes standard with
PCCNet and Modbus interface.
Regulation compliant
– Prototype tested: UL, CSA and CE
compliant.
Service
- InPower™ PC-based service tool available for
detailed diagnostics, setup, data logging and fault simulation.
Reliable design
– For reliable operations in harsh environment.
Multi-language support
Independent of PC/ laptop for setting up
Operator panel features
Operator panel features
– The operator panel, in addition to
the alternator, displays the Utility/ AC Bus data.
Operator/ display functions
- 320 x 240 pixels graphic LED backlight LCD with bar graph for
displaying electrical parameters
- Auto, manual, start, stop, fault reset and lamp test/panel lamp
switches
- Alpha-numeric display with pushbuttons
- LED lamps indicating genset running, remote start, not in auto,
common shutdown, common warning, manual run mode, auto
mode and stop
Paralleling control functions
- Digital frequency synchronization and voltage matching
- Isochronous kW and kvar load sharing controls
- Droop kW and kvar control
- Sync check
- Extended paralleling (Peak Shave/Base Load)
- Digital power transfer control (AMF) provides load transfer
operation in open or closed transition or soft (ramping) transfer
mode
Alternator data
- Line-to-neutral and line-to-line AC volts
- 3-phase AC current
- Frequency
- kW, kvar, power factor kVA (three phase and total)
Engine data
- DC voltage
- Engine speed
- Lube oil pressure
- Coolant temperature/ low level
- Comprehensive FAE data (where applicable)
Other data
- Genset model data
- Start attempts, starts, running hours, kW hours
- Load profile (operating hours at % load in 5% increments)
- Fault history
- Data logging and fault simulation (requires InPower)
Standard control functions
Digital governing
- Integrated digital electronic isochronous governor
- Temperature dynamic governing
Digital voltage regulation
- Integrated digital electronic voltage regulator
- 3-phase, 4-wire line-to-line sensing
- Configurable torque matching
AmpSentry AC protection
- AmpSentry protective relay
- Over current and short circuit shutdown
- Over current warning
- Single and three phase fault regulation
- Over and under voltage shutdown
- Over and under frequency shutdown
- Overload warning with alarm contact
- Reverse power and reverse var shutdown
- Field overload
Engine protection
- Battery voltage monitoring, protection and testing
- Over speed shutdown
- Low oil pressure warning and shutdown
- High coolant temperature warning and shutdown
- Low coolant level warning or shutdown
- Low coolant temperature warning
- Fail to start (over crank) shutdown
- Fail to crank shutdown
- Cranking lockout
- Sensor failure indication
- Low fuel level warning or shutdown
Control functions
- Time delay start and cool down
- Real time clock for fault and event time stamping
- Exerciser clock and time of day start/stop
- Data logging
- Cycle cranking
- Load shed/ dump as per configurable priority
- Configurable inputs and outputs (4)
- Remote emergency stop
Options
- Auxiliary output relays and remote annunciators
Technical data
Generator set specifications
Model
C1250 D5 P
C1500 D5 P
Prime Power Rating kVA
1250
1500
Output Voltage and Frequency
415 Volts, 50 Hz
415 Volts, 50 Hz
Power Factor
0.8 (lag)
0.8 (lag)
No. of phases
3 phase
3 phase
Engine specifications
Make
Cummins
Cummins
Model
KTA 50 G3
KTA 50 G8-I
No. of cylinders
16 ‘Vee’
16 ‘Vee’
Aspiration
Turbocharged-Aftercooled
Turbocharged-Aftercooled
Bore x Stroke
159 mm x 159 mm
159 mm x 159 mm
Displacement
50.3 ltrs
50.3 ltrs
Output - Prime
1470 bhp (1097 kWm)
1735 bhp (1294 kWm)
Fuel consumption @ 75% load with Radiator & Fan
190.8 ltr/hr
231 ltr/hr
Fuel consumption @ 100% load
251.8 ltr/hr
301.7 ltr/hr
Typical oil consumption @ 100% load
0.3 ltr/hr
0.35 ltr/hr
Total wet weight ( engine + radiator)
6824 kg
7205 kg
Length x Width x Height (engine)
2978 x 2080 x 1780 mm
2978 x 2080 x 1780 mm
Compression Ratio
13.9 : 1
14.9:1
Piston Speed
7.95 m/s
7.95 m/s
Governor / Class
Electronic / A1
Electronic / A1
Lubricating oil sytem capacity
177 ltrs
177 ltrs
Coolant capacity (engine + radiator)
440 ltrs
510 ltrs
Combustion air intake @ 100% load (+/- 5%)
81.6 m
3
/min
95.5 m
3
/min
Fan air flow across radiator
27357 ltrs/sec
28400 ltrs/sec
Exhaust Temperature
529
o
C
481
o
C
Alternator specifications
Make
Stamford
Stamford
Frame size / Model No.
HCK6Z
PI734C
Voltage Regulation
+ 0.5%
+ 0.5%
Insulation
Class H
Class H
Standard Enclosure
IP 23
IP 23
Winding Pitch
2 / 3 Pitch
2 / 3 Pitch
Stator Winding
Double layer lap
Double layer lap
Rotor
Dynamically balanced
Dynamically balanced
Wave form distortion
No load < 1.8 %, non distorting
No load < 1.8 %, non distorting
balanced linear load < 5 %
balanced linear load < 5 %
Telephone Interference Factor
Better than 50
Better than 50
Total Harmonic Factor
Better than 2%
Better than 2%
Conformance standards
IS
/
IEC 60
0
34
-1
, IS 1460, ISO 8528, ISO
3046, IS 13018, ISO 9001
Rating definitions
Prime Power (PRP):
Applicable for supplying power to varying electrical load
for unlimited hours. Prime Power (PRP) is in accordance
with ISO 8528. Ten
percent overload capability is available in accordance with ISO 3046,
IS 13018
-
Fuel consumption data is based on diesel having
specific gravity of 0.85 and conforming to IS:1460
-
Oil consumption data is based on oil having specific
gravity of 0.89 and meeting CH4 API categories
-
Fuel consumption tolerance is +5%
L
H
W
Genset Model
Rating
Length
Width
Height
Weight
(kVA)
(mm)
(mm)
(mm)
(kgs.) (Dry)
Std. Fuel Tank Capacity
(Ltrs
- External
)
C1250 D5 P
1250 kVA
6165
2235
2877
10800
C1500 D5 P
1500 kVA
6090
2075
2850
12250
Typical diesel genset dimensions*
990
990
Cummins India Limited
Power Generation Business Unit
Cummins India Office Campus
Tower-A, 6
th
Floor, S. No. 21,
Balewadi, Pune – 411 045 (India)
Email: cpgindia@cummins.com
www.cumminsindia.com
“Our energy working for you.”
© 201
5
Cummins Power Generation Inc. All rights reserved.
Visit our facebook page at :
Cummins Power Generation India
Authorised Representative
Cummins Power Generation Offices
Tel.: (080) 2325 9161 / 63, 2325 9165 / 67
Fax: (080) 2325 9164
Tel.: (0172) 224 0371-73
Fax: (0172) 224 0372
Tel.: (044) 2446 8110 / 2446 8113
Fax: (044) 2491 1120
Tel.: (0124) 391 0900-01
Fax : (0124) 391 0916
Tel.: (040) 2340 9970 / 2340 9980
Fax. (040) 2340 9990
Tel.: (0141) 236 4944
Fax: (0141) 403 8794
Bengaluru:
Chandigarh:
Chennai:
Gurgaon:
Hyderabad:
Jaipur:
Kolkata:
Lucknow:
Mohali:
Vadodara:
Tel.: (033) 2287 8065 / 2287 2481
Fax: (033) 2290 3839
Tel.: (0522) 230 5049 / 230 5059
Fax: (0522) 230 5035
Tel.: (0172) 224 0371 / 72 / 73
Fax: (0172) 224 0371 / 72 / 73
Tel.: (0265) 233 0627 / 3053627
Fax: (0265) 234 0623
Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand, AmpSentry, InPower and are trademarks of Cummins Power Generation.
Other company product or service names may be trademarks or service marks of others.
Specifications are subject to change without notice.
PGBU/0
0
3
/
K
50
1
25
0
-
1
500
kVA/
SA
/
NM
/
October
201
5